přílohy

field of application

specification of use

classification of functional integrity

electric fire alarms, including central

protection desks

supply cabling of exchange

not functional (an exchange having its own battery)

control cabling to elements that need only signal to switch over

to their fire function without the need of the cabling further on

P 15-R

command cabling to elements needing supply over the whole time of their

operation, as ensured by EPS (flap valves held in open position by EPS

tension, electric valves etc..) – during their functioning

P 15-R up to P 90-R (PH 90-R)

stationary and automatic, semi-stable

extinguishers, and aux. extinguishing

equipment

stable – powering fire pumps

P 30-R up to P 90-R (PH 90-R)

semi-stable

not functional (no power needed)

auxiliary – depending on project

no determination in advance (depending on the project)

equipment for drawing off heat

and smoke

fire fans

P 30-R

smoke flap valves

P 30-R

pumps for fire fighting water

min. P 30-R

door opening

acc. to chosen type, usually P 15-R

door closing

acc. to chosen type, usually P 15-R

broadcasting

P 30-R

emergency lights

according to Czech Standards

P 15-R up to P 60-R(PH 60-R)

according to European Standards

P 60-R (PH 60–R)

air conditioning

switching off air conditioning

P 15-R

fire elevator

P 45-R (PH 45-R)

evacuation elevator

P 45-R (PH 45-R)

openings for the air inlet

openings for air inlet depending on type,

usually P 15-R up to P 30-R

fans

fans for aeration of protected escape routes

P 15-R up to P 60-R (PH 60-R)

Currently requested classification of functional integrity

for some selected examples of installation of fire safe tracks for ensuring the fire security of buildings,

see ČSN 730848 – cable distributions with functional integrity

74

functional integrity